Skip to main content
SHARE
Publication

Immunity Study: Port Impedance Measurement of PMU and PCI testing under EMP

Publication Type
Conference Paper
Journal Name
Journal of Industrial Technology
Book Title
2022 IEEE/IAS Industrial and Commercial Power System Asia (I&CPS Asia)
Publication Date
Page Numbers
800 to 805
Issue
1
Publisher Location
New Jersey, United States of America
Conference Name
2022 IEEE IAS Industrial and Commercial Power System Asia (I&CPS Asia)
Conference Location
Shanghai, China
Conference Sponsor
IEEE
Conference Date
-

Phasor Measurement Units (PMUs) are critical for the Wide Area Measurement System (WAMS), especially for real-time grid monitoring, disturbance location, and situation awareness. Once they are damaged, the stable operation of the power system will be affected directly and greatly. Therefore, it is urgent and necessary to study their immunity to electromagnetic pulse (EMP) events. In this paper, an effective impedance measurement scheme is proposed for port impedance measurement of PMU. The equivalent non-uniform transmission line model is established to eliminate the impact of the fixture in the de-embedding process. Then circuit of pulsed current generator is established to generate damping sinusoid and double exponential wave applied to the port. Finally, by using measured impedance as a load of the generator, the voltage and current responses of different ports are calculated in the pulsed current injection (PCI) testing simulation. Results show that common-mode impedance is large and differential mode impedance is small. The critical condition will appear in the common mode for voltage and differential mode for current.