Skip to main content
SHARE
Publication

Model-based optimizations of packaged rooftop air conditioners using low global warming potential refrigerants...

by Bo Shen, Omar A Abdelaziz, Som S Shrestha, Ahmed F Elatar
Publication Type
Journal
Journal Name
International Journal of Refrigeration
Publication Date
Volume
TBD
Issue
TBD

Based on laboratory investigations for R-22 and R-410A alternative low GWP refrigerants in two baseline rooftop air conditioners (RTU), the DOE/ORNL Heat Pump Design Model was used to model the two RTUs and the models were calibrated against the experimental data. We compared the compressor efficiencies and heat exchanger performances. An efficiency-based compressor mapping method was developed. Extensive model-based optimizations were conducted to provide a fair comparison between all the low GWP candidates by selecting optimal configurations. The results illustrate that all the R-22 low GWP refrigerants will lead to slightly lower COPs. ARM-20B appears to be the best R-22 replacement at normal conditions. At higher ambient temperatures, ARM-20A exhibits better performance. All R-410A low GWP candidates will result in similar or better efficiencies than R-410A. R-32 has the best COP while requiring the smallest compressor. R-452B uses the closest compressor displacement volume and achieves the same efficiency as R-410A.