Skip to main content
SHARE
Publication

A Novel Model of Thyristor in Reverse Recovery Process for Current Interruption Test of HVDC Circuit Breakers...

by Zhonghao Dongye, Hua Zhang, Sheng Zheng, Fei Lu
Publication Type
Conference Paper
Book Title
2020 IEEE Transportation Electrification Conference & Expo (ITEC)
Publication Date
Page Numbers
858 to 862
Conference Name
IEEE Transportation Electrification Conference and Expo (ITEC)
Conference Location
Chicago, Illinois, United States of America
Conference Sponsor
IEEE
Conference Date
-

The high voltage thyristor is widely used in high voltage DC (HVDC) grids due to its large current capability. Recently, the high voltage thyristor is implemented to produce a high current in the HVDC circuit breaker (CB) testing process. Unfortunately, the reverse recovery process (RRP) of a thyristor could induce significant turn-off overvoltage and power losses, jeopardizing the safety of the devices. The existing models of a thyristor cannot describe such hard-switching transient accurately. Therefore, this paper divides this process into four stages based on the physical mechanism and proposes a novel cosine exponential (CE), simulating the voltage and current of the thyristor with analytical equations, which are derived from the equivalent circuit. Moreover, the extraction procedure of the proposed model is illustrated in this paper. Finally, we develop an HVDC CB test platform to validate the proposed model. Experimental results show that the proposed CE model can accurately predict the overvoltage with a relative error of less than 8% at various current varying rates.