Skip to main content
SHARE
Publication

Forced Oscillation Source Location in Power Systems Using MVMD-assisted DEF in TF Plane

by Jiang Tao, Bohan Liu, Bin Wang, Guodong Liu, Xue Li
Publication Type
Journal
Journal Name
IEEE Transactions on Power Systems
Publication Date
Page Numbers
1 to 12
Volume
39

Fast and accurate forced oscillation source location (FOSL) is critical for mitigating forced oscillations in power systems. To overcome the shortcomings of traditional dissipating energy flow (DEF) in decomposing the forced oscillation components from the measurement responses, a multivariate variational mode decomposition (MVMD)-assisted FOSL is proposed in this paper to locate the forced oscillation sources from measurements in time-frequency (TF) plane. The multi-channel measurement matrix of each generator is formed, then the multi-channel modes are decomposed from the formed multi-channel measurement matrix using the MVMD. Further, the intrinsic mode functions (IMFs) associated with the forced oscillation mode are distinguished from the decomposed modes according to the relative energy weights. With the distinguished IMFs, the MVMD-assisted DEF calculation method is developed to locate the forced oscillation source. Finally, the performance of the proposed method is evaluated using the simulation data of the WECC 179-bus test system and IEEE-NASPI Oscillation Source Location Contest as well as the actual PMU data of ISO New England. The results validated the effectiveness and accuracy of the proposed method in the FOSL.