Skip to main content
SHARE
Publication

Fundamental-Frequency Reactive Circulating Current Injection for Capacitor Voltage Balancing in Hybrid-MMC HVDC Systems Durin...

by Maozeng Lu, Jiabing Hu, Rong Zeng, Zhiyuan He
Publication Type
Journal
Journal Name
IEEE Transactions on Power Delivery
Publication Date
Page Numbers
1348 to 1357
Volume
33
Issue
3

This paper presents a comprehensive analysis and a novel solution for the discharge problem on the half-bridge submodules' (HBSMs') capacitors in the hybrid modular multilevel converter (MMC)-based high-voltage direct current transmission systems under a long-term (e.g., several minutes or longer) pole-to-ground fault condition. The mechanism of this issue is analyzed, and then a solution based on fundamental-frequency reactive circulating current (FFRCC) injection is proposed. The influence of FFRCC injection is analyzed in terms of the fluctuated arm capacitor energy and the current stress of semiconductors. Moreover, an enhanced arm voltage modulation method based on HBSMs and full-bridge submodules coordinate control is proposed to accelerate the capacitor voltage balance of HBSMs. Finally, the performance of the proposed control strategy is verified by the simulation results.