Skip to main content
SHARE
Publication

Multiple-Zone Variable Refrigerant Flow System Modeling and Equipment Performance Mapping ...

by Bo Shen, Clifford K Rice
Publication Type
Conference Paper
Publication Date
Page Numbers
420 to 427
Volume
118
Conference Name
ASHRAE winter conference 2011
Conference Location
Chicago, Illinois, United States of America
Conference Sponsor
ASHRAE
Conference Date
-

We developed a variable refrigerant flow (VRF) vapor compression system model, which has five indoor units, one outdoor unit and one water heater. The VRF system can run simultaneous space conditioning (cooling or heating) and water heating. The indoor units and outdoor unit use fin-&-tube coil heat exchangers, and the water heater uses a tube-in-tube heat exchanger. The fin-&-tube coil heat exchangers are modeled using a segment-by-segment approach and the tube-in-tube water heater is modeled using a phase-by-phase approach. The compressor used is a variable-speed rotary design. We calibrated our model against a manufacturer’s product literature. Based on the vapor compression system model, we investigated the methodology for generating VRF equipment performance maps, which can be used for energy simulations in TRNSYS and EnergyPlus, etc. In the study, the major independent variables for mapping are identified and the deviations between the simplified performance map and the actual equipment system simulation are quantified.