Performance analysis of single-phase immersion cooling system of data center using FC-40 dielectric fluid

by Muneeshwaran Murugan, Yueh-cheng Lin, Chi-chuan Wang
Publication Type
Journal
Journal Name
International Communications in Heat and Mass Transfer
Publication Date
Page Numbers
106843 to 106843
Volume
145
Issue
B

Immersion cooling technologies have become an emerging cooling method for data center cooling. The studies available in open literature dealt with immersion cooling performance of data servers using mineral oil, EC-100, and Opticool 872552, but the studies focusing on the performance of FC-40 dielectric fluid is not available. Therefore, this study aimed to develop a single-phase liquid immersion cooling system using FC-40 dielectric fluid for a 1U (44.45 mm height) data server. The present study experimentally investigated the influence of different design and operating parameters, including the inlet/outlet port configuration (T and Z configurations), the bypass effect, the flowrate (1–3 LPM), the heating load (200–600 W), the inlet fluid temperature (15–35 °C), the presence of suction fan with various arrangements, and different heat sink bases (solid base, vapor chamber and heat pipe base). The results showed that the T-configuration could provide a 12.6% and 0.5–2.8 °C reduction in thermal resistance and case temperature compared to the Z-configuration, respectively. Furthermore, the heat sink with heat pipe and vapor chamber base offered a minimum case temperature of 56.7 °C and 55.2 °C against the 60 °C experienced in the heat sink with flat plate base, respectively.